Turck Compact multiprotocol I/O module for Ethernet 8 Digital PNP Inputs and 8 Digital PNP 2 A Outputs – Image 1
Turck

Compact multiprotocol I/O module for Ethernet 8 Digital PNP Inputs and 8 Digital PNP 2 A Outputs

SKU: 100004251 Type: TBEN-LL-8DIP-8DOP
Available 3–5 business days delivery
€334.30 / pieces
€397.82 incl. VAT
Data sheet

Features

  • PROFINET device, EtherNet/IP device, Modbus TCP server, CC-Link IE field basic
  • Integrated Ethernet switch
  • Supports 10 Mbps/100 Mbps
  • 2 × M12, 4-pin, D-coded, Ethernet fieldbus connection
  • PROFINET S2 system redundancy
  • Glass fiber reinforced housing
  • Shock and vibration tested
  • Fully potted module electronics
  • Protection classes IP65, IP67, IP69K
  • M12, 5-pin, L-coded male connector for power supply
  • Galvanically isolated voltage groups support passive safety
  • ATEX zone 2/22
  • CCC-Ex
  • Input diagnostics per port
  • Max. 2 A per output
  • Output diagnostics per channel
  • Programmable ARGEE

EtherNet/IP™

Class 3 connections (TCP) 3 TCP
Addressing acc. to EtherNet/IP specification
Configuration Assembly Instance 106
Quick Connect (QC) < 150 ms
Output Assembly Instance 102
Input Assembly Instance 101
min. RPI 2 ms
Class 1 connections (CIP) 10 CIP
Device Level Ring (DLR) supported

General Information

Mounting 2 mounting holes ￿ 6.3 mm
ERR Green On No diagnostics available
ERR Red On Diagnostics available
ERR Undervoltage diagnosis response is parameter-dependent
MTTF 157 years acc. to SN 29500 (Ed. 99) 20 °C
Halogen free yes
L/A Green On Ethernet link (100 Mbps)
L/A Flashing Ethernet communication (100 Mbps)
L/A Yellow On Ethernet link (10 Mbps)
L/A Flashing Ethernet communication (10 Mbps)
L/A Off No Ethernet link
Ambient temperature from -40 to 70 °C
Connector material Nickel-plated brass
Material screw 303 stainless steel
Dimensions (L x W x H) 60.4 x 230.4 x 34.8 mm
Housing colour Black
Storage temperature from -40 to 85 °C
PWR LED response parameter (PWR) at V undervoltage = "red"
PWR 2
PWR Green On V and V power supply OK
PWR 1 2
PWR Red On V power supply off or V undervoltage
PWR 2 2
PWR Off V power supply off or V undervoltage
PWR 1 1
PWR LED response parameter (PWR) at V undervoltage = "green"
PWR Flashing V power supply off or V undervoltage
Window material Lexan
Altitude Max. 5000 m
LED Color Status Description
Housing material PA6-GF30
Material label Polycarbonate
BUS Green On Active connection to a client
BUS Flashing Steady flashing: ready for operation
BUS Sequence of 3 flashes in 2 seconds: FLC/ARGEE active
BUS Red On IP address conflict or Restore mode or Modbus timeout
BUS Flashing Blink/Wink command active
BUS Green/red Alternating Autonegotiation and/or waiting for DHCP/Boot-P addressing
BUS Off Power off
Degree of protection (IP) IP67
Degree of protection (IP) IP69K
Degree of protection (IP) IP65

Digital outputs

Output current per channel 2.0 A, short-circuit proof, max. 2.0 A per port
Output voltage 24 VDC from potential group
Output type PNP
Short circuit protection yes
Type of load EN 60947-5-1: DC-13
Type of output diagnostics Channel diagnostics
Output delay 1.3 ms
Output connectivity M12, 5-pin

Digital inputs

Switching threshold EN 61131-2 Typ 3, PNP
Number of channels 8
Input delay 2.5 ms
Low level signal current < 1.5 mA
Low-level signal voltage < 5 V
Electrical isolation Galvanically isolated to the fieldbus
Electrical isolation Voltage proof up 500 VDC
High level signal current > 2 mA
Input type PNP
Type of input diagnostics Group diagnostics
High level signal voltage > 11 V
Connectivity inputs M12, 5-pin

PROFINET

Version 2.35
Addressing DCP
Diagnostics acc. to PROFINET alarm handling
Network load class 3
Topology detection supported
Fast Start-Up (FSU) < 150 ms
MinCycleTime 1 ms
Automatic addressing supported
System redundancy S2
Media Redundancy Protocol (MRP) supported
Conformance class B (RT)

System data

ARGEE functionality Supported
Protocol detection automatic
BEEP functionality Supported
Transmission rate fieldbus 10/100 Mbps
Service interface Ethernet via XF1 or XF2
Connection technology fieldbus 2 × M12, 4-pin, D-coded

Modbus TCP

Addressing Static IP, DHCP
Number of TCP connections 8
Supported function codes FC1, FC2, FC3, FC4, FC6, FC15, FC16, FC23
Output register start address 2048 (0x0800 hex)
Input register start address 0 (0x0000 hex)

Supply

Sensor/actuator supply Ports X0-X3 powered by V1
Sensor/actuator supply short-circuit proof, 120 mA per port
Sensor/actuator supply Ports X4-X7 powered by V2
Power dissipation, typical ≤ 8 W
Admissible range 18…30 VDC Pass-through current XD1–XD2 max.
Admissible range 16 A per voltage group Device current max. 9 A per
Admissible range voltage group Total current V1 + V2 max. 11 A UL
Admissible range derating for > 55 °C: Total current max. 6 A per voltage group
Fault exclusion Yes, acc. to EN ISO 13849-2, appendix D.2
Electrical isolation galvanic isolation of the voltage groups V1 and V2,
Electrical isolation voltages up to 500 VAC
Operating current V1: max. 150 mA
Supply voltage 24 VDC
Connection technology power supply M12, L-coded

CC-Link

Acyclic SLMP communication Yes
Interfaces CC-Link IE Field Basic
IP change mechanism Yes
Message Transmission Yes
Max. occupied stations 1
Profile specification CSP+

Standard/Directive conformity

Shock test acc. to EN 60068-2-27
Approvals and certificates CEUKCAATEX zone 2/22
Approvals and certificates CCC-Ex
Approvals and certificates FCC statement,
Approvals and certificates UV resistant acc. to DIN EN ISO 4892-2A (2013)
Vibration test Acc. to EN 60068-2-6
Vibration test Acceleration up to 20 g
UL Certificate cULus LISTED 21 W2, Encl.Type 1 IND.CONT.EQ.
Drop and topple acc. to EN 60068-2-31/IEC 60068-2-32
Note on ATEX/IECEx The Quick Start Guide with information on use in Ex
Note on ATEX/IECEx areas must be observed.
Electromagnetic compatibility (EMC) Acc. to EN 61131-2

LED Status I/O

LED 8 … 15 Green On Output active
LED 8 … 15 Red On Output active with overload/short circuit
LED 8 … 15 Flashing Power overload at the corresponding port. Both port LEDs are flashing.
LED 8 … 15 Off Output inactive
LED 0…7 Green On Input active
LED 0…7 Red Flashing Power overload at the corresponding port. Both port LEDs are flashing.
LED 0…7 Off Input inactive

Power supply

Supply voltage 24 VDC