HomePosition SensorsUltrasonic Sensors100003168
Turck Ultrasonic Sensor Level Control – Image 1
Turck

Ultrasonic Sensor Level Control

SKU: 100003168 Type: LUS211-40-34-LI2UPN8-H1141
Available 3–5 business days delivery
€504.00 / pieces
€599.76 incl. VAT
Data sheet

Features

  • 4-digit, 2-colored, 12-segment display, rotatable by 180°
  • Housing is rotatable after mounting the process connection
  • ¾" NPT process connection
  • Blind zone: 0.5 cm
  • Range: 40 cm
  • Resolution: 0.5 mm
  • Aperture angle of sonic cone: ±15 °
  • 1 × switching output, PNP/NPN
  • 1 × analog output, 4…20 mA / 0…10 V / additional switching output, PNP/NPN
  • NO/NC programmable
  • Transmission of process value and parametrization via IO-link

Functional principle

Ultrasonic sensors capture a multitude of objects contactlessly and wear-free with ultrasonic waves. It does not matter whether the object is transparent or opaque, metallic or non-metallic, firm, liquid or powdery. Even environmental conditions such as spray, dust or rain hardly affect their function. The sonic cone diagram indicates the detection range of the sensor. In accordance with standard EN 60947-5-7, quadratic targets in a range of sizes (20 × 20 mm, 100 × 100 mm) and a round rod with a diameter of 27 mm are used. Important: The detection ranges for other targets may differ from those for standard targets due to the different reflection properties and geometries.

Electrical data

Standby delay ≤ 300 ms
Load resistance voltage output ≥ 8 kΩ
Response time typical < 60 ms
Current output 4…20 mA
Switching frequency up to 5 Hz
Voltage drop at Ie ≤ 2.5 V
No-load current I0 ≤ 150 mA
Adjustment option Capacitive Sensor
Adjustment option IO-Link
Hysteresis ≤ 50 mm
Short circuit protection yes
Polarity protection yes
Output function NO/NC, PNP/NPN, analog output
Load resistance current output ≤ 0.5 kΩ
Output 1 Switching output or IO-Link mode
Output 2 Analog output
Communication protocol IO-Link
Residual current ≤ 0.1 mA
Operating voltage UB from 18 to 33 VDC
Voltage output from 0 to 10 V
Lastwiderstand (U-Ausgang) ≤ 1000 Ω

IO-Link

Maximum Cable Length 20 m
IO-Link port type Class A
Communication mode COM 2 (38.4 kBaud)
Function pin 4 IO-Link
Function Pin 2 DI
Frame type 2.2
Process data width 32 bit
Minimum cycle time 5 ms
Profile support Smart Sensor Profile
Included in the SIDI GSDML Yes
Switchpoint information 4 bit
IO-Link specification V 1.1
Measured value information 15 bit

Ultrasonic data

Edge lengths of the nominal actuator 20 mm
Temperature drift ± 1.5% of full scale% of full scale
Function Proximity switch
Resolution 0.5 mm
Approach speed ≤ 3 m/s
Overrun Speed ≤ 1.3 m/s
Ultrasound frequency 320 kHz
Range from 0.005 to 0.4 m
Minimum switching range 5 mm
Minimum measuring range 50 mm

Tests/approvals

Vibration resistance 20 g, 10…2000 Hz, sine, 3 axes, 30 min/axis according to IEC 60068-2-6
Type code Ident no. Dimension drawing
Declaration of conformity EN ISO/IEC EN 60947-5-7
Shock test 50 g, 11 ms, half sine, 3 axes according to IEC
Shock test 60068-2-27
Approvals cULus
Approvals CE

Mechanical data

Elektrischer Anschluss Connector, M12 × 1, 4-wire
Pressure resistance 0.5…5 bar
Ambient temperature from -25 to 70 °C
Process connection 3/4″ NPT
Transducer material Plastic, Epoxyd resin and PU foam
Design Smooth barrel, LUS
Radiation direction straight
Housing material Stainless-steel/Plastic, 1.4404 (AISI 316L)/Grilamid
Housing material TR90 UV
Degree of protection (IP) IP67
Degree of protection (IP) IP69K
Abmessung Ø 38 x 127.1 mm