HomeAccessoriesConnectors7580225
Turck Frequency Transducer/Pulse Counter 1-channel – Image 1
Turck

Frequency Transducer/Pulse Counter 1-channel

SKU: 7580225 Type: IM12-FI01-1SF-1I1R-C0/24VDC
Available 3–5 business days delivery
€296.90 / pieces
€353.31 incl. VAT
Data sheet

Features

  • Input circuits monitored for wire-break and short-circuit
  • Parameterized via PC
  • Complete galvanic isolation
  • Removable screw terminals
  • ATEX use in Zone 2, cUL
  • SIL 2

Output circuits

Switching current per output ≤ 2 A
Contact quality AgNi
Output current Source/sink (10…30 V) 0/4…20 mA
Switching capacity per output ≤ 500 VA/60 W
Switching frequency up to 15 Hz
Load resistance current output ≤ 0.8 kΩ
Output circuits 1 x relay (change-over)
Output switching voltage relay ≤ 30 VDC / ≤ 250 VAC

NAMUR input

Wire breakage threshold ≤ 0.06 mA
Switch-on threshold 1.75 mA
Short-circuit current 8.2 mA
Input resistance 1 kΩ
Switch-off threshold 1.55 mA
Short-circuit threshold ≥ 6.4 mA
No-load voltage 8.2 VDC
NAMUR EN 60947-5-6
Line Resistance ≤ 50 Ω

Displays/Operating elements

Operational readiness Green
Error indication red

Allgemein

Monitoring range/Setting range 0.0006…1,200,000 rpm
Nominal voltage 24 VDC
Operating voltage UB from 10 to 30 VDC
Power consumption up to 3 VA

Galvanic separation

Test voltage 2.5 kV RMS
A1A-A1D 300 V RMS acc. to EN 50178 and EN 61010-1
E1,E2-E3 375 V peak value acc. to EN 60079-11
Ignition protection type SIL 2 acc. to IEC 61508
E1,E2 supply voltage 375 V peak value acc. to EN 60079-11
E3 supply voltage 375 V peak value acc. to EN 60079-11
A1A-E3 300 V RMS acc. to EN 50178 and EN 61010-1
A1A supply voltage 300 V RMS acc. to EN 50178 and EN 61010-1
Important note For Ex-applications the values specified in the corresponding Ex certificates (ATEX, IECEx, UL, etc.) apply.
Important note If the device is used in applications to achieve functional safety according to IEC 61508, the safety
Important note manual must be used. Information in the data sheet
Important note are not valid for functional safety.

3-wire input

1-signal 5...30 VDC
0-signal 0...3VDC
No-load voltage 12 VDC

External signal source

1-signal 5…30 VDC
0-signal 0…3 VDC

Response characteristic

Temperature drift ≤ 0.0025 % of full scale/K
Reference temperature 23 °C

Mechanical data

Altitude Up to 2000 m above sea
Altitude level
Pollution degree II
Overvoltage category II (EN 61010-1)