IPFSensor flow, air, calorimetric, 187x75x475mm, R1 1/2", 18-36V DC, 4-20mA, M12 plug connector 5-pin, plastic PC, pressure resistance 16bar, with display, parameterization, RS485, MBus – Image 1
IPF

Sensor flow, air, calorimetric, 187x75x475mm, R1 1/2", 18-36V DC, 4-20mA, M12 plug connector 5-pin, plastic PC, pressure resistance 16bar, with display, parameterization, RS485, MBus

SKU: SL94F001
Available3–5 business days delivery
€1,551.50 / pieces
€1,846.28 incl. VAT

These are our list prices.Get an individual quote within 24 h.

Request a quote
Data sheet(DE)

Features

  • The function of the flow sensor is based on the calorimetric principle. The sensor is heated by a few degrees Celsius from the inside compared to the flow medium into which it protrudes. If the medium flows, the heat generated in the sensor is dissipated by the medium. The temperature generated in the sensor is measured and compared with the temperature of the medium, which is also measured. The flow state for each medium can be derived from the temperature difference obtained. Applications for these sensors include compressed air consumption measuring devices.

Electrical features

Number of poles of interface connection5
Design of the interface connectionPlug-in connection M12
Coding of the interface connectionA
Elektrischer AnschlussConnector M12
Setting procedureParameterization
Load resistance (current output)500 kOhm
Type of analogy output4…20 mA
Measurement principlecalorimetric
Supported communication interfaceMBus | Modbus RTU
IndicationTFT display
No-load current120 mA
Number of poles of the electrical connection5
Protection functionsShort circuit protection | Reverse polarity protection
Coding of the electrical connectionA
Operating voltage (DC)18 - 36 V
Measurement accuracy± 1.5 % of measuring range ± 0.3 % of measuring range end

Other features

Reference medium / objectAir
Humidity in operation (non-condensing)95 %
ApplicationPneumatic applications

More

IPF Product Group725 compressed air and leakage measurement
packaging dimensions500 x 165 x 230 mm
Customs tariff number90268020
WEEE number40951076
Reach-compliantYes
RoHS‑compliantYes
gross weight2466 g

Installation / Disposal

DisposalWEEE number according to § 6 para. 3 ElektroG: 40951076
InstallationMounting / installation may only be carried out by a qualified electrician!

Classification

ETIM 8EC002580 Flow monitoring device

Mechanical features

Measurement range flow velocity0,18 - 185 m/s
Height186.9 mm
Width475 mm
Pressure resistance16 bar
Ambient temperaturefrom -20 to 70 °C
Process connectionR1 1/2 inch
Length75 mm
Housing materialPlastic PC
Material of measuring transducerStainless steel 1.4301
Medium temperaturefrom -30 to 80 °C
DesignCuboid, integrated measuring section
Measurement range flow volume16,66 - 12166,66 l/min
Degree of protection (IP)IP65

Other

Process connectionR1
DesignQuader
Connector typeM12

Safety warnings

  • Before initial operation, please make sure to follow all safety instructions that may be provided in the product information.
  • Never use these devices in applications where the safety of a person depends on their functionality.
  • Any software, drivers or IODD files that may be required to operate your device can be downloaded free of charge from our homepage: www.ipf-electronic.com