HomeSensor AnalyticsFieldbus Modules100000360
Turck Block Module for EtherNet/IP and CIP Safety Safe Digital Inputs and Outputs, Standard Universal Digital Channels, IO-Link Master Ports – Image 1
Turck

Block Module for EtherNet/IP and CIP Safety Safe Digital Inputs and Outputs, Standard Universal Digital Channels, IO-Link Master Ports

SKU: 100000360 Type: TBIP-L4-FDIO1-2IOL
Available 3–5 business days delivery
€858.00 / pieces
€1,021.02 incl. VAT
Data sheet

Features

  • Ethernet/IP device
  • Integrated Ethernet switch
  • 10 Mbps/100 Mbps supported
  • 2 × M12, 4-pin, D-coded, Ethernet fieldbus connection
  • Glass fiber reinforced housing
  • Shock and vibration tested
  • Fully potted module electronics
  • Protection classes IP65, IP67, IP69K
  • 4-pin 7/8″ male connector for power supply
  • ATEX zone 2/22
  • CCC-Ex
  • Two secure digital SIL3-inputs
  • Two secure digital SIL3 channels as FDI or FDO (PP, PM)
  • Four secure digital SIL3 FDI channels
  • 2 IO-Link Master V1.1 slots Figure 1

General Information

Mounting 2 mounting holes ￿ 6.3 mm
Mounting The data sheet serves as advance information. For
Mounting definitive values see the corresponding product
Mounting manual. In this respect, no liability for completeness
Mounting and accuracy can be applied to the content of this
Mounting data sheet.
Mounting 7/8″ Power Supply
Mounting Note
Mounting Power supply cable (example):
Mounting RKM43-1-RSM43
Mounting ID number 6914312
Halogen free yes
ETH1/ETH2NSMS Green ON Ethernet Link (100 Mbps)
ETH1/ETH2NSMS flashing Ethernet communication (100 Mbps)
ETH1/ETH2NSMS OFF No Ethernet linkGreen On Active connection to a master
ETH1/ETH2NSMS flashing Connection has been established but
ETH1/ETH2NSMS not fully completed
ETH1/ETH2NSMS Red On Communication Error
ETH1/ETH2NSMS flashing One or more I/O connections
ETH1/ETH2NSMS have the time-out status.
ETH1/ETH2NSMS Red/Green Alternating Faulty self-test or configurationGreen On Diagnostics disabled
ETH1/ETH2NSMS Green Flashing When used as a stand-alone
ETH1/ETH2NSMS device: Device is in protective mode,
ETH1/ETH2NSMS an EtherNet/IP™ client is accessing
ETH1/ETH2NSMS the standard I/Os.
ETH1/ETH2NSMS Red On Critical error
ETH1/ETH2NSMS Red Flashing Correctable error
ETH1/ETH2NSMS Green/ Flashing alternately Faulty self-test or configuration
ETH1/ETH2NSMS Red
Ambient temperature from -40 to 70 °C
Connector material Nickel-plated brass
Material screw 303 stainless steel
Dimensions (L x W x H) 60.4 x 230.5 x 38.8 mm
Housing colour Black
Storage temperature from -40 to 85 °C
PWR Green On V power supply OK
PWR 1
PWR Off V power supply off or V undervoltage
PWR 1 1
Window material Lexan
Altitude Max. 5000 m
LED Color Status Description
Housing material PA6-GF30
Material label Polycarbonate
Degree of protection (IP) IP67
Degree of protection (IP) IP69K
Degree of protection (IP) IP65

LED Status I/O

12, 14 (IO-Link Port 1 and 2) SIO Mode Green ON Digital Input signal is present
12, 14 (IO-Link Port 1 and 2) SIO Mode OFF No input signal
0…3 Green ON Channel active
0…3 flashing Self test
0…3 Red ON Discrepancy
0…3 flashing Cross circuit
4…7 Green ON Channel active
4…7 flashing Self test (input only)
4…7 Red ON Discrepancy, overload (output only)
4…7 flashing Cross circuit
8…11 Green ON Channel active
8…11 Red ON Overload (output only)
8…11 flashing Overload of supply
8…11 Green/Red alternating Channel active and overload of supply (input only)
13, 15 Green ON Digital input or output active
13, 15 Red ON Output active with overload/short circuit
13, 15 flashing Overload of supply
13, 15 OFF Input or output inactive

Safety outputs (OSSDs)

Actuator power supply 2 A (resistive)
Actuator power supply 1 A (inductive)
Output current in off state < 5 V
Output current in off state < 1 mA
Output current in off state suitable for inputs according to EN 61131-2 Type 1
Test pulse, typical 0.5 ms
Test pulse, typical 1.25 ms
Sensor supply M12, 5-pin
Test pulse, maximum 500 ms
Max. output current The load must be mechanically or electrically inert to
Max. output current tolerate the test pulses.
Max. output current When configured as a PPM switching output the
Max. output current negative pole of the load should be wired to the Mterminal of the corresponding output (Pin 2).
Additional Information M12, 5-pin
Interval between 2 test pulses, minimum 250 ms
Interval between 2 test pulses, minimum Power supply V AUX1/T1 max. 2 A
Interval between 2 test pulses, minimum Please consider derating as shown in figure 1
Interval between 2 test pulses, minimum C4, C5: FSO 0 max. 2 A; 500 mA per output
Interval between 2 test pulses, minimum C6: V AUX1 max. 2 A
Interval between 2 test pulses, minimum C7: FSO1 max. 2 A
Connectivity inputs 2.5 ms
Output connectivity 0.5 A, short-circuit proof,
Output connectivity max. 2 A (resistive)/ 1 A (inductive) all std. outputs

System data

Web server integrated
Transmission rate fieldbus 10/100 Mbps
Service interface Ethernet via P1 or P2
Connection technology fieldbus 2 × M12, 4-pin, D-coded

IO-Link

Transmission rate 4.8 kbps (COM 1) / 38.4 kbps (COM 2) / 230 kbps
Transmission rate (COM 3)
Number of channels 2
IO-Link port type Class A and Class B
Frame type supports all specified frame types
Supported devices Max. 32 bytes in/32 bytes out per port
Power supply Power supply V AUX1 max. 2 A
Power supply Please consider derating as shown in figure 1
IO-Link specification V 1.1

EtherNet/IP™

Addressing acc. to EtherNet/IP specification
Quick Connect (QC) (Not supported according to ODVA specifications)
Class 1 connections (CIP) 3 CIP
Device Level Ring (DLR) supported

Safety Inputs OSSD

Max. tolerance test pulse width 1 ms
Low-level signal voltage EN 61131-2 Type 1 ( < 5 V; < 0.5 mA)
Max. OSSD supply per channel 2 A per C0, C1, C2, C3,
Max. OSSD supply per channel 1.5 A at 70 °C
Max. OSSD supply per channel Please consider derating as shown in figure 1
High level signal voltage EN 61131-2 Type 1 ( > 15 V; > 2 mA)
Interval between 2 test pulses, minimum 20 ms at 1 ms test pulse width
Interval between 2 test pulses, minimum 15 ms at 0.5 ms test pulse width

Supply

Power dissipation, typical ≤ 5 W
Admissible range 20.4…28.8 VDC
Electrical isolation galvanic isolation of the voltage groups V1 and V2,
Electrical isolation voltages up to 500 VAC
Supply voltage 24 VDC
Connection technology power supply 7/8″, 4-pin

Safety Data

PL according to EN ISO 13849-1 Level e
Category according to ISO 13849-1:2008 4
Useful Lifetime 20 years (EN ISO 13849-1)
SIL according to IEC 61508 3

Safety Inputs floating/antivalent

Test pulse, typical 0.6 ms
Sensor supply Power supply V AUX1/T1 max. 2 A
Sensor supply Please consider derating as shown in figure 1
Test pulse, maximum 0.8 ms
Additional Information No connection to external potential allowed
Max. cable length up to 1 m
Max. loop resistance < 150 Ω
Interval between 2 test pulses, minimum 900 ms

Standard/Directive conformity

Directive 2006/42/EC Machine Directive
Directive 2014/30/EC EMC Directive
Directive 2014/35/EC Low Voltage Directive
Shock test acc. to EN 60068-2-27
Approvals and certificates CEUKCAATEX zone 2/22
Approvals and certificates CCC-Ex
Approvals and certificates FCC statement,
Approvals and certificates UV resistant acc. to DIN EN ISO 4892-2A (2013)
Vibration test Acc. to EN 60068-2-6
Vibration test Acceleration up to 20 g
UL Certificate cULus LISTED 21 W2, Encl.Type 1 IND.CONT.EQ.
Drop and topple acc. to EN 60068-2-31/IEC 60068-2-32
Note on ATEX/IECEx The Quick Start Guide with information on use in Ex
Note on ATEX/IECEx areas must be observed.
Electromagnetic compatibility (EMC) Acc. to EN 61131-2

Power supply

Supply voltage 24 VDC