HomeSensor AnalyticsFieldbus Modules100000360
TurckBlock Module for EtherNet/IP and CIP Safety Safe Digital Inputs and Outputs, Standard Universal Digital Channels, IO-Link Master Ports – Image 1
Turck

Block Module for EtherNet/IP and CIP Safety Safe Digital Inputs and Outputs, Standard Universal Digital Channels, IO-Link Master Ports

SKU: 100000360 Type: TBIP-L4-FDIO1-2IOL
Available3–5 business days delivery
€858.00 / pieces
€1,021.02 incl. VAT

These are our list prices.Get an individual quote within 24 h.

Request a quote
Data sheet

Features

  • Ethernet/IP device
  • Integrated Ethernet switch
  • 10 Mbps/100 Mbps supported
  • 2 × M12, 4-pin, D-coded, Ethernet fieldbus connection
  • Glass fiber reinforced housing
  • Shock and vibration tested
  • Fully potted module electronics
  • Protection classes IP65, IP67, IP69K
  • 4-pin 7/8″ male connector for power supply
  • ATEX zone 2/22
  • CCC-Ex
  • Two secure digital SIL3-inputs
  • Two secure digital SIL3 channels as FDI or FDO (PP, PM)
  • Four secure digital SIL3 FDI channels
  • 2 IO-Link Master V1.1 slots Figure 1

General Information

Mounting2 mounting holes ￿ 6.3 mm
MountingThe data sheet serves as advance information. For
Mountingdefinitive values see the corresponding product
Mountingmanual. In this respect, no liability for completeness
Mountingand accuracy can be applied to the content of this
Mountingdata sheet.
Mounting7/8″ Power Supply
MountingNote
MountingPower supply cable (example):
MountingRKM43-1-RSM43
MountingID number 6914312
Halogen freeyes
ETH1/ETH2NSMSGreen ON Ethernet Link (100 Mbps)
ETH1/ETH2NSMSflashing Ethernet communication (100 Mbps)
ETH1/ETH2NSMSOFF No Ethernet linkGreen On Active connection to a master
ETH1/ETH2NSMSflashing Connection has been established but
ETH1/ETH2NSMSnot fully completed
ETH1/ETH2NSMSRed On Communication Error
ETH1/ETH2NSMSflashing One or more I/O connections
ETH1/ETH2NSMShave the time-out status.
ETH1/ETH2NSMSRed/Green Alternating Faulty self-test or configurationGreen On Diagnostics disabled
ETH1/ETH2NSMSGreen Flashing When used as a stand-alone
ETH1/ETH2NSMSdevice: Device is in protective mode,
ETH1/ETH2NSMSan EtherNet/IP™ client is accessing
ETH1/ETH2NSMSthe standard I/Os.
ETH1/ETH2NSMSRed On Critical error
ETH1/ETH2NSMSRed Flashing Correctable error
ETH1/ETH2NSMSGreen/ Flashing alternately Faulty self-test or configuration
ETH1/ETH2NSMSRed
Ambient temperaturefrom -40 to 70 °C
Connector materialNickel-plated brass
Material screw303 stainless steel
Dimensions (L x W x H)60.4 x 230.5 x 38.8 mm
Housing colourBlack
Storage temperaturefrom -40 to 85 °C
PWRGreen On V power supply OK
PWR1
PWROff V power supply off or V undervoltage
PWR1 1
Window materialLexan
AltitudeMax. 5000 m
LEDColor Status Description
Housing materialPA6-GF30
Material labelPolycarbonate
Degree of protection (IP)IP67
Degree of protection (IP)IP69K
Degree of protection (IP)IP65

LED Status I/O

12, 14 (IO-Link Port 1 and 2) SIO ModeGreen ON Digital Input signal is present
12, 14 (IO-Link Port 1 and 2) SIO ModeOFF No input signal
0…3Green ON Channel active
0…3flashing Self test
0…3Red ON Discrepancy
0…3flashing Cross circuit
4…7Green ON Channel active
4…7flashing Self test (input only)
4…7Red ON Discrepancy, overload (output only)
4…7flashing Cross circuit
8…11Green ON Channel active
8…11Red ON Overload (output only)
8…11flashing Overload of supply
8…11Green/Red alternating Channel active and overload of supply (input only)
13, 15Green ON Digital input or output active
13, 15Red ON Output active with overload/short circuit
13, 15flashing Overload of supply
13, 15OFF Input or output inactive

Safety outputs (OSSDs)

Actuator power supply2 A (resistive)
Actuator power supply1 A (inductive)
Output current in off state< 5 V
Output current in off state< 1 mA
Output current in off statesuitable for inputs according to EN 61131-2 Type 1
Test pulse, typical0.5 ms
Test pulse, typical1.25 ms
Sensor supplyM12, 5-pin
Input delayC4, C5: FSO 0 max. 2 A; 500 mA per input
Input delayC6: V AUX1 max. 2 A
Input delayC7: FSO1 max. 2 A
Input delayPlease consider derating as shown in figure 1
Test pulse, maximum500 ms
Max. output currentThe load must be mechanically or electrically inert to
Max. output currenttolerate the test pulses.
Max. output currentWhen configured as a PPM switching output the
Max. output currentnegative pole of the load should be wired to the Mterminal of the corresponding output (Pin 2).
Additional InformationM12, 5-pin
Interval between 2 test pulses, minimum250 ms
Interval between 2 test pulses, minimumPower supply V AUX1/T1 max. 2 A
Interval between 2 test pulses, minimumPlease consider derating as shown in figure 1
Interval between 2 test pulses, minimumC4, C5: FSO 0 max. 2 A; 500 mA per output
Interval between 2 test pulses, minimumC6: V AUX1 max. 2 A
Interval between 2 test pulses, minimumC7: FSO1 max. 2 A
Connectivity inputs2.5 ms
Output connectivity0.5 A, short-circuit proof,
Output connectivitymax. 2 A (resistive)/ 1 A (inductive) all std. outputs

System data

Web serverintegrated
Transmission rate fieldbus10/100 Mbps
Service interfaceEthernet via P1 or P2
Connection technology fieldbus2 × M12, 4-pin, D-coded

IO-Link

Transmission rate4.8 kbps (COM 1) / 38.4 kbps (COM 2) / 230 kbps
Transmission rate(COM 3)
Number of channels2
IO-Link port typeClass A and Class B
Frame typesupports all specified frame types
Supported devicesMax. 32 bytes in/32 bytes out per port
Power supplyPower supply V AUX1 max. 2 A
Power supplyPlease consider derating as shown in figure 1
IO-Link specificationV 1.1

EtherNet/IP™

Addressingacc. to EtherNet/IP specification
Quick Connect (QC)(Not supported according to ODVA specifications)
Class 1 connections (CIP)3 CIP
Device Level Ring (DLR)supported

Safety Inputs OSSD

Max. tolerance test pulse width1 ms
Low-level signal voltageEN 61131-2 Type 1 ( < 5 V; < 0.5 mA)
Max. OSSD supply per channel2 A per C0, C1, C2, C3,
Max. OSSD supply per channel1.5 A at 70 °C
Max. OSSD supply per channelPlease consider derating as shown in figure 1
High level signal voltageEN 61131-2 Type 1 ( > 15 V; > 2 mA)
Interval between 2 test pulses, minimum20 ms at 1 ms test pulse width
Interval between 2 test pulses, minimum15 ms at 0.5 ms test pulse width

Supply

Admissible range20.4…28.8 VDC
Power dissipation, typical≤ 5 W
Electrical isolationgalvanic isolation of the voltage groups V1 and V2,
Electrical isolationvoltages up to 500 VAC
Supply voltage24 VDC
Connection technology power supply7/8″, 4-pin

Safety Data

PL according to EN ISO 13849-1Level e
Category according to ISO 13849-1:20084
Useful Lifetime20 years (EN ISO 13849-1)
SIL according to IEC 615083

Safety Inputs floating/antivalent

Test pulse, typical0.6 ms
Sensor supplyPower supply V AUX1/T1 max. 2 A
Sensor supplyPlease consider derating as shown in figure 1
Test pulse, maximum0.8 ms
Additional InformationNo connection to external potential allowed
Max. cable lengthup to 1 m
Max. loop resistance< 150 Ω
Interval between 2 test pulses, minimum900 ms

Standard/Directive conformity

Directive2006/42/EC Machine Directive
Directive2014/30/EC EMC Directive
Directive2014/35/EC Low Voltage Directive
Shock testacc. to EN 60068-2-27
Approvals and certificatesCEUKCAATEX zone 2/22
Approvals and certificatesCCC-Ex
Approvals and certificatesFCC statement,
Approvals and certificatesUV resistant acc. to DIN EN ISO 4892-2A (2013)
Vibration testAcc. to EN 60068-2-6
Vibration testAcceleration up to 20 g
UL CertificatecULus LISTED 21 W2, Encl.Type 1 IND.CONT.EQ.
Drop and toppleacc. to EN 60068-2-31/IEC 60068-2-32
Note on ATEX/IECExThe Quick Start Guide with information on use in Ex
Note on ATEX/IECExareas must be observed.
Electromagnetic compatibility (EMC)Acc. to EN 61131-2

Power supply

Supply voltage24 VDC

Other

Housing materialKunststoff