HomeSensor AnalyticsFieldbus Modules100000758
TurckCompact Multiprotocol I/O Module for Ethernet 8 Digital PNP Inputs and 8 Digital PNP 2 A Outputs – Image 1
Turck

Compact Multiprotocol I/O Module for Ethernet 8 Digital PNP Inputs and 8 Digital PNP 2 A Outputs

SKU: 100000758 Type: TBEN-L5-8DIP-8DOP-01
Available3–5 business days delivery
€375.80 / pieces
€447.20 incl. VAT

These are our list prices.Get an individual quote within 24 h.

Request a quote
Data sheet

Features

  • PROFINET device, EtherNet/IP device, Modbus TCP server, CC-Link IE field basic
  • Integrated Ethernet switch
  • Supports 10 Mbps/100 Mbps
  • 2 × M12, 4-pin, D-coded, Ethernet fieldbus connection
  • PROFINET S2 system redundancy
  • Glass fiber reinforced housing
  • Shock and vibration tested
  • Fully potted module electronics
  • Protection classes IP65, IP67, IP69K
  • 7/8″ male connector for power supply, 5pin
  • Galvanically isolated voltage groups
  • ATEX zone 2/22
  • CCC-Ex
  • Input diagnostics per port
  • Max. 2 A per output
  • Output diagnostics per channel
  • Ports C4–C7: Pin 1 not connected
  • Programmable ARGEE

System data

ARGEE Engineering Version2.0.25.0
Web serverDefault: 192.168.1.254
ARGEE functionalitySupported
Protocol detectionautomatic
ARGEE Firmware Version3.3.2.0
Transmission rate fieldbus10/100 Mbps
Service interfaceEthernet via P1 or P2
Connection technology fieldbus2 × M12, 4-pin, D-coded

EtherNet/IP™

Class 3 connections (TCP)3 TCP
Addressingacc. to EtherNet/IP specification
Configuration Assembly Instance106
Quick Connect (QC)< 150 ms
Output Assembly Instance102
Input Assembly Instance101
min. RPI2 ms
Class 1 connections (CIP)10 CIP
Device Level Ring (DLR)supported

General Information

Mounting2 mounting holes Ø 6.3 mm
ERRGreen On No diagnostics available
ERRRed On Diagnostics available
ERRUndervoltage diagnosis response is parameter dependent
MTTF179 years acc. to SN 29500 (Ed. 99) 20 °C
Halogen freeyes
Ambient temperaturefrom -40 to 70 °C
Connector materialNickel-plated brass
Material screw303 stainless steel
Dimensions (L x W x H)60.4 x 230.5 x 38.8 mm
Housing colourBlack
ETH1/ETH2Green On Ethernet Link (100 Mbps)
ETH1/ETH2Flashing Ethernet communication (100 Mbps)
ETH1/ETH2yellow On Ethernet link (10 Mbps)
ETH1/ETH2Flashing Ethernet communication (10 Mbps)
ETH1/ETH2Off No Ethernet link
Storage temperaturefrom -40 to 85 °C
PWRLED response parameter (PWR) at V undervoltage = "red"
PWR2
PWRGreen On V and V power supply OK
PWR1 2
PWRRed On V power supply off or V undervoltage
PWR2 2
PWROff V power supply off or V undervoltage
PWR1 1
PWRLED response parameter (PWR) at V undervoltage = "green"
PWRFlashing V power supply off or V undervoltage
Window materialLexan
AltitudeMax. 5000 m
LEDColor Status Description
Housing materialPA6-GF30
Material labelPolycarbonate
BUSGreen On Active connection to a master
BUSFlashing Steady flashing: Ready
BUSSequence of 3 flashes in 2 seconds: FLC/ARGEE active
BUSRed On IP-address conflict or Restore Mode or Modbus timeout
BUSFlashing Blink/Wink command active
BUSGreen/Red Alternating Autonegotiation and/or waiting for DHCP/Boot-P addressing
BUSOff Power off
Degree of protection (IP)IP67
Degree of protection (IP)IP69K
Degree of protection (IP)IP65

Digital outputs

Output current per channel2.0 A per port, short-circuit proof
Output voltage24 VDC from potential group
Output typePNP
Short circuit protectionyes
Type of loadEN 60947-5-1: DC-13
Type of output diagnosticsChannel diagnostics
Output delay1.3 ms
Output connectivityM12, 5-pin

Digital inputs

Switching thresholdEN 61131-2 Typ 3, PNP
Number of channels8
Input delay2.5 ms
Low level signal current< 1.5 mA
Low-level signal voltage< 5 V
Electrical isolationGalvanically isolated to the fieldbus
Electrical isolationVoltage proof up 500 VDC
High level signal current> 2 mA
Input typePNP
Type of input diagnosticsGroup diagnostics
High level signal voltage> 11 V
Connectivity inputsM12, 5-pin

PROFINET

Version2.35
AddressingDCP
Diagnosticsacc. to PROFINET alarm handling
Network load class3
Topology detectionsupported
Fast Start-Up (FSU)< 150 ms
MinCycleTime1 ms
Automatic addressingsupported
System redundancyS2
Media Redundancy Protocol (MRP)supported
Conformance classB (RT)

Modbus TCP

AddressingStatic IP, DHCP
Number of TCP connections8
Supported function codesFC1, FC2, FC3, FC4, FC6, FC15, FC16, FC23
Output register start address2048 (0x0800 hex)
Input register start address0 (0x0000 hex)

CC-Link

Acyclic SLMP communicationYes
InterfacesCC-Link IE Field Basic
IP change mechanismYes
Message TransmissionYes
Max. occupied stations1
Profile specificationCSP+

Supply

Admissible range18…30 VDC
Admissible rangeTotal current max. 9 A per voltage group
Admissible rangeTotal current V1 + V2 max. 11 A
Power dissipation, typical≤ 8 W
Sensor/actuator supplysupply of ports C0-C3 from V1
Sensor/actuator supplyshort-circuit proof, 120 mA per port
Electrical isolationgalvanic isolation of the voltage groups V1 and V2,
Electrical isolationvoltages up to 500 VAC
Operating currentV1: max. 150 mA
Supply voltage24 VDC
Connection technology power supply7/8″, 5-pin

Standard/Directive conformity

Shock testacc. to EN 60068-2-27
Approvals and certificatesCEUKCAATEX zone 2/22
Approvals and certificatesCCC-Ex
Approvals and certificatesUV resistant acc. to DIN EN ISO 4892-2A (2013)
Vibration testAcc. to EN 60068-2-6
Vibration testAcceleration up to 20 g
Drop and toppleacc. to EN 60068-2-31/IEC 60068-2-32
Note on ATEX/IECExThe Quick Start Guide with information on use in Ex
Note on ATEX/IECExareas must be observed.
Electromagnetic compatibility (EMC)Acc. to EN 61131-2

LED Status I/O

LED 8 … 15Green ON Output active
LED 8 … 15Red ON Output active with overload/short circuit
LED 8 … 15flashing Power overload at the corresponding port. Both port LEDs are flashing.
LED 8 … 15OFF Output inactive
LED 0…7Green ON Input active
LED 0…7Red Flashing Power overload at the corresponding port. Both port LEDs are flashing.
LED 0…7OFF Input inactive

Power supply

Supply voltage24 VDC

Other

Housing materialKunststoff