Turck
Turck
Compact Multiprotocol I/O Module for Ethernet 8 Digital PNP Inputs and 8 Digital PNP 2 A Outputs
SKU: 100000758 Type: TBEN-L5-8DIP-8DOP-01
Available 3–5 business days delivery
€375.80 / pieces
€447.20 incl. VAT
Features
- • PROFINET device, EtherNet/IP device, Modbus TCP server, CC-Link IE field basic
- • Integrated Ethernet switch
- • Supports 10 Mbps/100 Mbps
- • 2 × M12, 4-pin, D-coded, Ethernet fieldbus connection
- • PROFINET S2 system redundancy
- • Glass fiber reinforced housing
- • Shock and vibration tested
- • Fully potted module electronics
- • Protection classes IP65, IP67, IP69K
- • 7/8″ male connector for power supply, 5pin
- • Galvanically isolated voltage groups
- • ATEX zone 2/22
- • CCC-Ex
- • Input diagnostics per port
- • Max. 2 A per output
- • Output diagnostics per channel
- • Ports C4–C7: Pin 1 not connected
- • Programmable ARGEE
System data
| ARGEE Engineering Version | 2.0.25.0 |
| Web server | Default: 192.168.1.254 |
| ARGEE functionality | Supported |
| Protocol detection | automatic |
| ARGEE Firmware Version | 3.3.2.0 |
| Transmission rate fieldbus | 10/100 Mbps |
| Service interface | Ethernet via P1 or P2 |
| Connection technology fieldbus | 2 × M12, 4-pin, D-coded |
EtherNet/IP™
| Class 3 connections (TCP) | 3 TCP |
| Addressing | acc. to EtherNet/IP specification |
| Configuration Assembly Instance | 106 |
| Quick Connect (QC) | < 150 ms |
| Output Assembly Instance | 102 |
| Input Assembly Instance | 101 |
| min. RPI | 2 ms |
| Class 1 connections (CIP) | 10 CIP |
| Device Level Ring (DLR) | supported |
General Information
| Mounting | 2 mounting holes Ø 6.3 mm |
| ERR | Green On No diagnostics available |
| ERR | Red On Diagnostics available |
| ERR | Undervoltage diagnosis response is parameter dependent |
| MTTF | 179 years acc. to SN 29500 (Ed. 99) 20 °C |
| Halogen free | yes |
| Ambient temperature | from -40 to 70 °C |
| Connector material | Nickel-plated brass |
| Material screw | 303 stainless steel |
| Dimensions (L x W x H) | 60.4 x 230.5 x 38.8 mm |
| Housing colour | Black |
| ETH1/ETH2 | Green On Ethernet Link (100 Mbps) |
| ETH1/ETH2 | Flashing Ethernet communication (100 Mbps) |
| ETH1/ETH2 | yellow On Ethernet link (10 Mbps) |
| ETH1/ETH2 | Flashing Ethernet communication (10 Mbps) |
| ETH1/ETH2 | Off No Ethernet link |
| Storage temperature | from -40 to 85 °C |
| PWR | LED response parameter (PWR) at V undervoltage = "red" |
| PWR | 2 |
| PWR | Green On V and V power supply OK |
| PWR | 1 2 |
| PWR | Red On V power supply off or V undervoltage |
| PWR | 2 2 |
| PWR | Off V power supply off or V undervoltage |
| PWR | 1 1 |
| PWR | LED response parameter (PWR) at V undervoltage = "green" |
| PWR | Flashing V power supply off or V undervoltage |
| Window material | Lexan |
| Altitude | Max. 5000 m |
| LED | Color Status Description |
| Housing material | PA6-GF30 |
| Material label | Polycarbonate |
| BUS | Green On Active connection to a master |
| BUS | Flashing Steady flashing: Ready |
| BUS | Sequence of 3 flashes in 2 seconds: FLC/ARGEE active |
| BUS | Red On IP-address conflict or Restore Mode or Modbus timeout |
| BUS | Flashing Blink/Wink command active |
| BUS | Green/Red Alternating Autonegotiation and/or waiting for DHCP/Boot-P addressing |
| BUS | Off Power off |
| Degree of protection (IP) | IP67 |
| Degree of protection (IP) | IP69K |
| Degree of protection (IP) | IP65 |
Digital outputs
| Output current per channel | 2.0 A per port, short-circuit proof |
| Output voltage | 24 VDC from potential group |
| Output type | PNP |
| Short circuit protection | yes |
| Type of load | EN 60947-5-1: DC-13 |
| Type of output diagnostics | Channel diagnostics |
| Output delay | 1.3 ms |
| Output connectivity | M12, 5-pin |
Digital inputs
| Switching threshold | EN 61131-2 Typ 3, PNP |
| Number of channels | 8 |
| Low level signal current | < 1.5 mA |
| Low-level signal voltage | < 5 V |
| Electrical isolation | Galvanically isolated to the fieldbus |
| Electrical isolation | Voltage proof up 500 VDC |
| High level signal current | > 2 mA |
| Input type | PNP |
| Type of input diagnostics | Group diagnostics |
| High level signal voltage | > 11 V |
| Connectivity inputs | M12, 5-pin |
PROFINET
| Version | 2.35 |
| Addressing | DCP |
| Diagnostics | acc. to PROFINET alarm handling |
| Network load class | 3 |
| Topology detection | supported |
| Fast Start-Up (FSU) | < 150 ms |
| MinCycleTime | 1 ms |
| Automatic addressing | supported |
| System redundancy | S2 |
| Media Redundancy Protocol (MRP) | supported |
| Conformance class | B (RT) |
Modbus TCP
| Addressing | Static IP, DHCP |
| Number of TCP connections | 8 |
| Supported function codes | FC1, FC2, FC3, FC4, FC6, FC15, FC16, FC23 |
| Output register start address | 2048 (0x0800 hex) |
| Input register start address | 0 (0x0000 hex) |
Supply
| Sensor/actuator supply | supply of ports C0-C3 from V1 |
| Sensor/actuator supply | short-circuit proof, 120 mA per port |
| Power dissipation, typical | ≤ 8 W |
| Admissible range | 18…30 VDC |
| Admissible range | Total current max. 9 A per voltage group |
| Admissible range | Total current V1 + V2 max. 11 A |
| Electrical isolation | galvanic isolation of the voltage groups V1 and V2, |
| Electrical isolation | voltages up to 500 VAC |
| Operating current | V1: max. 150 mA |
| Supply voltage | 24 VDC |
| Connection technology power supply | 7/8″, 5-pin |
CC-Link
| Acyclic SLMP communication | Yes |
| Interfaces | CC-Link IE Field Basic |
| IP change mechanism | Yes |
| Message Transmission | Yes |
| Max. occupied stations | 1 |
| Profile specification | CSP+ |
Standard/Directive conformity
| Shock test | acc. to EN 60068-2-27 |
| Approvals and certificates | CEUKCAATEX zone 2/22 |
| Approvals and certificates | CCC-Ex |
| Approvals and certificates | UV resistant acc. to DIN EN ISO 4892-2A (2013) |
| Vibration test | Acc. to EN 60068-2-6 |
| Vibration test | Acceleration up to 20 g |
| Drop and topple | acc. to EN 60068-2-31/IEC 60068-2-32 |
| Note on ATEX/IECEx | The Quick Start Guide with information on use in Ex |
| Note on ATEX/IECEx | areas must be observed. |
| Electromagnetic compatibility (EMC) | Acc. to EN 61131-2 |
LED Status I/O
| LED 8 … 15 | Green ON Output active |
| LED 8 … 15 | Red ON Output active with overload/short circuit |
| LED 8 … 15 | flashing Power overload at the corresponding port. Both port LEDs are flashing. |
| LED 8 … 15 | OFF Output inactive |
| LED 0…7 | Green ON Input active |
| LED 0…7 | Red Flashing Power overload at the corresponding port. Both port LEDs are flashing. |
| LED 0…7 | OFF Input inactive |
Power supply
| Supply voltage | 24 VDC |