HomeSensor AnalyticsFieldbus Modules100000759
Turck Compact Multiprotocol I/O Module for Ethernet 16 Digital PNP Outputs – Image 1
Turck

Compact Multiprotocol I/O Module for Ethernet 16 Digital PNP Outputs

SKU: 100000759 Type: TBEN-L5-16DOP-01
Available 3–5 business days delivery
€388.90 / pieces
€462.79 incl. VAT
Data sheet

Features

  • PROFINET device, EtherNet/IP device, Modbus TCP server, CC-Link IE field basic
  • Integrated Ethernet switch
  • Supports 10 Mbps/100 Mbps
  • 2 × M12, 4-pin, D-coded, Ethernet fieldbus connection
  • PROFINET S2 system redundancy
  • Glass fiber reinforced housing
  • Shock and vibration tested
  • Fully potted module electronics
  • Protection classes IP65, IP67, IP69K
  • 7/8″ male connector for power supply, 5pin
  • Galvanically isolated voltage groups
  • ATEX zone 2/22
  • CCC-Ex
  • Max. 2 A per output
  • Output diagnostics per channel
  • Ports C0–C7: Pin 1 not connected
  • Programmable ARGEE

System data

ARGEE Engineering Version 2.0.25.0
Web server Default: 192.168.1.254
ARGEE functionality Supported
Protocol detection automatic
ARGEE Firmware Version 3.3.2.0
Transmission rate fieldbus 10/100 Mbps
Service interface Ethernet via P1 or P2
Connection technology fieldbus 2 × M12, 4-pin, D-coded

EtherNet/IP™

Class 3 connections (TCP) 3 TCP
Addressing acc. to EtherNet/IP specification
Configuration Assembly Instance 106
Quick Connect (QC) < 150 ms
Output Assembly Instance 102
Input Assembly Instance 101
min. RPI 2 ms
Class 1 connections (CIP) 10 CIP
Device Level Ring (DLR) supported

General Information

Mounting 2 mounting holes Ø 6.3 mm
ERR Green On No diagnostics available
ERR Red On Diagnostics available
ERR Undervoltage diagnosis response is parameter dependent
MTTF 172 years acc. to SN 29500 (Ed. 99) 20 °C
Halogen free yes
Ambient temperature from -40 to 70 °C
Connector material Nickel-plated brass
Material screw 303 stainless steel
Dimensions (L x W x H) 60.4 x 230.5 x 38.8 mm
Housing colour Black
ETH1/ETH2 Green On Ethernet Link (100 Mbps)
ETH1/ETH2 Flashing Ethernet communication (100 Mbps)
ETH1/ETH2 yellow On Ethernet link (10 Mbps)
ETH1/ETH2 Flashing Ethernet communication (10 Mbps)
ETH1/ETH2 Off No Ethernet link
Storage temperature from -40 to 85 °C
PWR LED response parameter (PWR) at V undervoltage = "red"
PWR 2
PWR Green On V and V power supply OK
PWR 1 2
PWR Red On V power supply off or V undervoltage
PWR 2 2
PWR Off V power supply off or V undervoltage
PWR 1 1
PWR LED response parameter (PWR) at V undervoltage = "green"
PWR Flashing V power supply off or V undervoltage
Window material Lexan
Altitude Max. 5000 m
LED Color Status Description
Housing material PA6-GF30
Material label Polycarbonate
BUS Green On Active connection to a master
BUS Flashing Steady flashing: Ready
BUS Sequence of 3 flashes in 2 seconds: FLC/ARGEE active
BUS Red On IP-address conflict or Restore Mode or Modbus timeout
BUS Flashing Blink/Wink command active
BUS Green/Red Alternating Autonegotiation and/or waiting for DHCP/Boot-P addressing
BUS Off Power off
Degree of protection (IP) IP67
Degree of protection (IP) IP69K
Degree of protection (IP) IP65

LED Status I/O

LED 0 … 15 Green ON Output active
LED 0 … 15 Red ON Output active with overload/short circuit
LED 0 … 15 flashing Power overload at the corresponding port. Both port LEDs are flashing.
LED 0 … 15 OFF Output inactive

Digital outputs

Output current per channel 2.0 A per port, short-circuit proof
Number of channels 16
Output voltage 24 VDC from potential group
Electrical isolation Galvanically isolated to the fieldbus
Electrical isolation Voltage proof up 500 VDC
Output type PNP
Short circuit protection yes
Type of load EN 60947-5-1: DC-13
Type of output diagnostics Channel diagnostics
Output delay 1.3 ms
Output connectivity M12, 5-pin

PROFINET

Version 2.35
Addressing DCP
Diagnostics acc. to PROFINET alarm handling
Network load class 3
Topology detection supported
Fast Start-Up (FSU) < 150 ms
MinCycleTime 1 ms
Automatic addressing supported
System redundancy S2
Media Redundancy Protocol (MRP) supported
Conformance class B (RT)

Modbus TCP

Addressing Static IP, DHCP
Number of TCP connections 8
Supported function codes FC1, FC2, FC3, FC4, FC6, FC15, FC16, FC23
Output register start address 2048 (0x0800 hex)
Input register start address 0 (0x0000 hex)

CC-Link

Acyclic SLMP communication Yes
Interfaces CC-Link IE Field Basic
IP change mechanism Yes
Message Transmission Yes
Max. occupied stations 1
Profile specification CSP+

Supply

Power dissipation, typical ≤ 10 W
Admissible range 18…30 VDC
Admissible range Total current max. 9 A per voltage group
Admissible range Total current V1 + V2 max. 11 A
Electrical isolation galvanic isolation of the voltage groups V1 and V2,
Electrical isolation voltages up to 500 VAC
Operating current V1: max. 150 mA
Supply voltage 24 VDC
Connection technology power supply 7/8″, 5-pin

Standard/Directive conformity

Shock test acc. to EN 60068-2-27
Approvals and certificates CEUKCAATEX zone 2/22
Approvals and certificates CCC-Ex
Approvals and certificates UV resistant acc. to DIN EN ISO 4892-2A (2013)
Vibration test Acc. to EN 60068-2-6
Vibration test Acceleration up to 20 g
Drop and topple acc. to EN 60068-2-31/IEC 60068-2-32
Note on ATEX/IECEx The Quick Start Guide with information on use in Ex
Note on ATEX/IECEx areas must be observed.
Electromagnetic compatibility (EMC) Acc. to EN 61131-2

Power supply

Supply voltage 24 VDC