Turck
Turck
I/O Hub for Connection of Digital Signals to IO-Link Master 8 Universal Digital Channels, 8 M8 Ports
SKU: 100002595 Type: TBIL-S3-8DXP
Available 3–5 business days delivery
€144.50 / pieces
€171.95 incl. VAT
Features
- • Glass fiber reinforced housing
- • Shock and vibration tested
- • Fully potted module electronics
- • Protection classes IP65, IP67, IP69K
General Information
| Mounting | 2 mounting holes, Ø 4.3 mm |
| MTTF | 429 years acc. to SN 29500 (Ed. 99) 20 °C |
| IO-Link | Green OFF Power off |
| IO-Link | Flashing IO-Link communication OK, |
| IO-Link | valid process data is being sent or received |
| IO-Link | Red ON IO-Link communication or module error |
| IO-Link | invalid process data or diagnosis enabled |
| Ambient temperature | from -40 to 70 °C |
| Dimensions (L x W x H) | 32 x 144.3 x 32 mm |
| Housing colour | Black |
| LED display | Color Status Description |
| Storage temperature | from -40 to 85 °C |
| Altitude | Max. 5000 m |
| Housing material | PA6-GF30 |
| Degree of protection (IP) | IP67 |
| Degree of protection (IP) | IP69K |
| Degree of protection (IP) | IP65 |
Digital outputs
| Output current per channel | 0.5 A |
| Electrical isolation | 500 VDC |
| Output type | PNP |
| Short circuit protection | yes |
| Type of load | Resistive, inductive, lamp load |
| Type of output diagnostics | Channel diagnostics |
| Output delay | 0.35 ms |
| Output connectivity | M8 |
IO-Link
| Transmission rate | COM 2/38.4 kbps |
| IO-Link port type | Class A |
| Frame type | 2,6 |
| Connectivity IO-Link | 1 × M12 |
| IO-Link specification | V 1.1 |
Supply
| Sensor/actuator supply | Class A supply from V1 |
| Sensor/actuator supply | Short-circuit proof, 4 A per port |
| Admissible range | 18…30 VDC |
| Operating current | 120 mA |
| Supply voltage | 24 VDC |
| Connection technology power supply | M12 |
Digital inputs
| Number of channels | 8 |
| Sensor supply | C0–C3, C4–C7 max 0.5 A per group |
| Low-level signal voltage | -3…5 VDC (EN 61131-2, type 1 and 3) |
| Max. input current | 15 mA |
| Type of input diagnostics | Channel diagnostics |
| High level signal voltage | 11…30 VDC (EN 61131-2, type 1 and 3) |
| Connectivity inputs | M8 |
I/O LED Status
| Cx – Cx | Green ON Input or output active |
| Cx – Cx | Red ON Output active with overload/short circuit |
| Cx – Cx | Flashing Power overload at the corresponding port. Both port LEDs are flashing. |
| Cx – Cx | OFF Input or output inactive |
| Type code | Ident no. Dimension drawing |
Standard/Directive conformity
| Shock test | acc. to IEC 60068-2-27 |
| Approvals and certificates | CEUKCAUV resistant acc. to DIN EN ISO 4892-2A (2013) |
| Vibration test | Acc. to IEC 60068-2-6 |
| UL Certificate | cULus LISTED 21 W2, Encl.type 1 IND.CONT.EQ. |
Power supply
| Supply voltage | 24 VDC |