HomeSensor AnalyticsIIoT DevicesHUB-IO100
in.hubHUB-IO100 – Image 1
in.hub

HUB-IO100

SKU: HUB-IO100 Type: A5000036
Available3–5 business days delivery
€549.00 / pieces
€653.31 incl. VAT

These are our list prices.Get an individual quote within 24 h.

Request a quote
Data sheet

Analogue input AIN

Sampling interval≥50 ms*
Input resistance101 kΩ
Resolution12 bit
Operating modesCurrent, voltage
Operating modesProtective functions: Overload protection
Operating modesIn 20 mA mode, the current is limited to 22–30 mA
Measuring range0–11 V / 0–24 mA

Data

MemoryRAM: 256 MB DDR3L, Flash: 512 MB SLC NAND
Typical power consumption5 W
ProtocolsOPC UA server + client
ProtocolsMQTT broker server + client
ProtocolsModbus TCP/IP broker client + server
Max. power consumption24 W
HousingPlastic (polyamide), black, flammability class UL 94 V0
Data interfacesUSB1: Host (Micro-USB)
Data interfacesUSB2: Device (USB-A)
Data interfacesEthernet: 100 Mbit/s
Data interfaces3× status LEDs
Data interfacesBackplane bus
Connections for peripheral devices6× digital input/output
Connections for peripheral devices6× digital input
Connections for peripheral devices4× analogue input
Connections for peripheral devices2× analogue output
Dimensions (L x W x H)139 mm × 100 mm × 25 mm
Current supply24 V DC, max. 1 A
Weight150 g
Operating SystemSIINEOS IIoT operating system for configuration and data visualization
ProcessorNXP® i.MX 6ULL
Degree of protection (IP)IP20

Digital input DIN

Switching thresholdBetween 5 V and 15 V
BandwidthFrom 6 Hz (with 12 channels, 2 edges) to 150 Hz (with 1 channel, 1 edge)*
Input resistanceTyp. 7 kΩ, max. 200 mW
Permissible input voltage range–3 to 30 V
ConformityEN61131-2 Type 1

Configuration of DIO as a digital input

Switching thresholdBetween 5 V and 11 V
Pull-down currentTyp. 2 mA
ConformityEN61131-2 Type 1/3

SIINEOS

Pre-installed softwareFlexPlorer: Live data visualization
Pre-installed softwareAzure IoT Hub Connector: Connector to the Microsoft® IoT platform
Pre-installed softwareCloud of Things Connector: Connector to the Telekom® IoT platform
Pre-installed softwareNumCorder: Recording of scanned or entered barcodes / serial numbers
Pre-installed softwareOPC UA server: Counterpart to the OPC UA client, setting up of a server–client structure with one device
Pre-installed softwarePromEx: Database configuration of VictoriaMetrics and Prometheus

Storage

Storage100 MB
Data exportVictoriaMetrics
Recording intervalMinimum 1 second

Backplane bus

CommunicationModbus RTU
Voltage on the backplane busVoltage of the power supply unit minus 0.5 V
Voltage on the backplane busSwitchable in the signals of the master gateway

Analogue output AO

Max. output current25 mA
Voltage drop to 24 VMax. 2 V

Ambient Conditions

HumidityStorage: 10% to 95% RH, non-condensing
HumidityOperation: 20% to 90% RH, non-condensing
Operating altitudeMax. 2,000 m above sea level
Temperature rangeStorage: –40°C to 85°C
Temperature rangeOperation: 0°C to 50°C

USB connections

Max. power output USB22.5 W (500 mA) with 24 V supply
Support forFull, high and low speed (480, 12 and 1.5 Mbit/s)

Other

Max. output currentTyp. 120 mA
Switching interval≥50 ms*
ConformityEN61131-2 nominal current 0.1 A
Power supplyFrom 24 V
Power supplyProtective functions: Overload protection, reverse-current protection
Voltage drop to 24 VMax. 1 V