HomeSensor AnalyticsIO-LinkVL530100
IPFLogic module, 100x118x22mm, AND/OR, 8gang, 10-30V DC, terminals on sensor side, terminals on control side, IP40, plastic, IO-Link, bounce protection – Image 1
IPF

Logic module, 100x118x22mm, AND/OR, 8gang, 10-30V DC, terminals on sensor side, terminals on control side, IP40, plastic, IO-Link, bounce protection

SKU: VL530100
Available3–5 business days delivery
€159.00 / pieces
€189.21 incl. VAT

These are our list prices.Get an individual quote within 24 h.

Request a quote
Data sheet(DE)

Features

  • IO-Link interface bounce protection by pulse stretching
  • Combining digital signals directly on the machine can help to minimize costs and effort considerably. A classic application is linking different signals directly in the field. This avoids long cable runs between many individual devices, significantly minimizes the wiring effort and reduces the need for control inputs. All input signals on the logic modules are visualized by integrated LEDs and are electrically decoupled from each other. This reliably prevents influences from one device to the other. The modules' outputs are overload-proof and the pending signal is also indicated via an LED. Along with logical input signal links such as AND or OR, versions with signal change control are also available. The ipf logic modules are available for top-hat rail mounting or as field modules. Thanks to this and the robust housing, which is characterized by a high degree of protection against the ingress of dust and water, our devices can be used in all areas of machines, systems and tools.

More

IPF Product Group800 miscellaneous
packaging dimensions149 x 128 x 28 mm
Customs tariff number85365005
WEEE number40951076
Reach-compliantYes
RoHS‑compliantYes
gross weight125 g

Installation / Disposal

DisposalWEEE number according to § 6 para. 3 ElektroG: 40951076
InstallationMounting / installation may only be carried out by a qualified electrician!

Electrical features

Number of inputs per logic unit8
Number of logic units2
IndicationLED display
LogicAND/OR
Output logicA1 = E1 ∧ E2 ∧ E3 ∧ E4 ∧ E5 ∧ E6 ∧ E7 ∧ E8 A2 = E1 ∨ E2 ∨ E3 ∨ E4 ∨ E5 ∨ E6 ∨ E7 ∨ E8
Design of electrical connection AClamped terminal connection
Design of electrical connection BClamped terminal connection
Operating voltage (DC)10 - 30 V
Rated switch current100 mA
Operating voltagefrom 10 to 30 V

Mechanical features

Height90 mm
Width22.5 mm
Mounting methodTop hat rail
Ambient temperaturefrom -20 to 70 °C
Length118 mm
Housing materialPlastic
Degree of protection (IP)IP40
Abmessung118x22.5x90mm

Safety warnings

  • Before initial operation, please make sure to follow all safety instructions that may be provided in the product information.
  • Never use these devices in applications where the safety of a person depends on their functionality.
  • Any software, drivers or IODD files that may be required to operate your device can be downloaded free of charge from our homepage: www.ipf-electronic.com