HomeSensor AnalyticsIO-Link100052134
TurckBL20 Efficiency Line Module 4 IO-Link Master Channels, 32 Bytes of I/O Data 4 Configurable Digital Channels, PNP, Channel Diagnostics, 0.5 A – Image 1
Turck

BL20 Efficiency Line Module 4 IO-Link Master Channels, 32 Bytes of I/O Data 4 Configurable Digital Channels, PNP, Channel Diagnostics, 0.5 A

SKU: 100052134 Type: BL20-EL-4IOL-10
Available3–5 business days delivery
€143.80 / pieces
€171.12 incl. VAT

These are our list prices.Get an individual quote within 24 h.

Request a quote
Data sheet

Features

  • Fieldbus-independent
  • Electronics and connection technology in one housing
  • Connectivity: Push-in terminals
  • Protection class IP20
  • LEDs indicate status and diagnostic
  • Electronics galvanically separated from the field level via optocouplers
  • 4-channel IO-Link master acc. to specification V1.1
  • 4 universal digital channels, PNP, channel diagnostics, 0.5 A

Functional principle

Electronics and connection technology are integrated in the housing. A base module is not needed. Economy modules and modules with separate electronics and connection technology can be fitted into a station, provided the base modules feature tension spring connections. The use of gateways makes economy modules completely independent from the higher level fieldbus.

Allgemein

Nominal voltage Vo24 VDC
Nominal current from module bus≤ 40 mA
Rated voltage from the supply terminal24 VDC
Admissible range18…30 VDC
Output voltage24 VDC
Power dissipation, typical≤ 2 W
Load resistance, resistive> 48 Ω
Nominal current from field supply≤ 80 mA
Low level signal current< 1.5 mA DI/< 5 mA SIO
Low-level signal voltage< 5 V
Input connectivityPush-in
Electrical isolationelectronics to the field level
Switching frequency, inductive< 2 Hz
Max. field supply current10 A
High level signal current2.1…3.7 mA DI/5…11 mA SIO
Output typePNP
Input typePNP
Switching frequency, resistive< 200 Hz
Number of channels4 /4
Type of loadResistive, inductive
High level signal voltage> 11 V
Load resistance, inductive< 1.2 H
Output delay3 ms
Output connectivityPush-in

IO-Link

IO-Link channels 1…4 SIO modeOFF Status channel x = 0 (OFF)
IO-Link channels 1…4 SIO modeGREEN ON Status channel x = 1 (ON)
Transmission rate4.8 kbps (COM 1) / 38.4 kbps (COM 2) / 230 kbps
Transmission rate(COM 3)
MTTF388 years acc. to SN 29500 (Ed. 99) 20 °C
IO-Link port typeClass A
Number of output bytes32
Relative humidity15…95 %, no condensation allowed
Frame typesupports all specified framet types
IO-Link channels 1…4 IO-Link modeOFF Status channel x = 0 (OFF)
IO-Link channels 1…4 IO-Link modeGREEN FLASHING IO-Link communication active
IO-Link channels 1…4 IO-Link modevalid process data
IO-Link channels 1…4 IO-Link modeRED ON No IO-Link communication
IO-Link channels 1…4 IO-Link modeand/or module error, invalid process data
IO-Link channels 1…4 IO-Link modeRED FLASHING IO-Link communication active
Number of diagnostics bytes8
Number of input bytes32
LEDDColor Status MeaningOFF No error message or diagnostics active.
LEDDRED ON Failure of module bus communication. Check if more than 2 adjacent electronic modules are pulled. Relevant modules are located
LEDDbetween gateway and this module.
LEDDRED FLASHING (0.5 Hz) Upcoming module diagnostics
Ambient temperaturefrom 0 to 55 °C
Supported devicesmax. 30 byte input / 30 byte output
Shock testAcc. to IEC 60068-2-27
XSG channels 5…8OFF Status channel x = 0 (OFF)
XSG channels 5…8GREEN ON Status channel x = 1 (ON)
XSG channels 5…8RED FLASHING (0.5 Hz) Short-circuit output channel x
Dimensions (L x W x H)13 x 128.9 x 74.6 mm
ApprovalsCE
Vibration testAcc. to EN 61131
Drop and toppleAcc. to IEC 60068-2-31
Storage temperaturefrom -40 to 85 °C
Number of parameter bytes32
IO-Link specificationV 1.1
Electromagnetic compatibility (EMC)Acc. to EN 61131-2
Degree of protection (IP)IP20