IPF

IPF
amplifier flow, 110x75x55mm, 24V DC, Change-over contact (NO/NC), Clamp, IP20, Plastic, With LED display
SKU: SV550800
Available3–5 business days delivery
€261.70 / pieces
€311.42 incl. VAT
These are our list prices.Get an individual quote within 24 h.
Request a quoteFeatures
- including Screwdriver
- The function of the flow sensor is based on the calorimetric principle. The probe is heated up from the inside a few degrees Celsius in relation to the flow medium, in which it protrudes. When the medium flows, the heat generated in the probe is dissipated through the medium. The temperature within the sensor is measured and compared with the likewise measured medium temperature. From the obtained temperature difference the flow state of each medium can be derived. These sensors are applied in areas such as monitoring of cooling systems, ventilation systems, pump dry running by checking the presence of liquid or gas flows.
Electrical features
| Switching voltage | 250 V |
| Amplifier for flow sensors | Yes |
| Elektrischer Anschluss | Clamped terminal connection |
| Switching power | 1000 VA |
| Type of switch function | Change-over contact (NO/NC) |
| Power consumption | 8 VA |
| Indication | LED display |
| No-load current | 34 mA |
| Number of channels | 1 |
| Number of changeover contacts | 2 |
| Operating voltage (DC) | 24 V |
| Rated switch current | 4000 mA |
| Switching voltage AC | 250 V |
| Switching voltage DC | 60 V |
More
| IPF Product Group | 300 flow sensors |
| packaging dimensions | 143 x 74 x 74 mm |
| Customs tariff number | 85365019 |
| WEEE number | 40951076 |
| Reach-compliant | Yes |
| RoHS‑compliant | Yes |
| gross weight | 250 g |
Installation / Disposal
| Disposal | WEEE number according to § 6 para. 3 ElektroG: 40951076 |
| Installation | Mounting / installation may only be carried out by a qualified electrician! |
Classification
| ETIM 8 | EC001485 Isolation amplifier |
Mechanical features
| Height | 75 mm |
| Width | 55 mm |
| Mounting method | Top hat rail |
| Ambient temperature | from -20 to 60 °C |
| Length | 110 mm |
| Housing material | Plastic |
| Design | Cuboid |
| Degree of protection (IP) | IP20 |
Other
| Design | Quader |
Ipf Kdb FLTE1200(DE)
ipf_kdb_FLTE1200_de.pdf
Ipf Adb SV550800(DE)
ipf_adb_SV550800_de.pdf
Ipf Bda SV55X800(DE)
ipf_bda_SV55x800_de.pdf
Ipf Ukc SV550800(DE)
ipf_ukc_SV550800_de.pdf
Ipf Mcd SV550800(DE)
ipf_mcd_SV550800_de.pdf
Ipf Cek SV550800(DE)
ipf_cek_SV550800_de.pdf
Ipf Ulz Standard M1
ipf_ulz_standard_m1.pdf
Ipf Ccc Standard M1
ipf_ccc_standard_m1.pdf
Ipf Csa Standard M1
ipf_csa_standard_m1.pdf
Ipf Fly Fluidtechnik(DE)
ipf_fly_Fluidtechnik_de.pdf
Ipf Whp Fluidtechnik(DE)
ipf_whp_Fluidtechnik_de.pdf
Ipf Whp Stroemungssensoren(DE)
ipf_whp_Stroemungssensoren_de.pdf
Safety warnings
- Before initial operation, please make sure to follow all safety instructions that may be provided in the product information.
- Never use these devices in applications where the safety of a person depends on their functionality.