SKU: 100029807 Type: TTM-206A-CF-LIUPN-H1140-L600
Available3–5 business days delivery
€157.20 / pieces
€187.07 incl. VAT

These are our list prices.Get an individual quote within 24 h.

Request a quote
Data sheet

Features

  • Miniature design
  • Factory setting 0…150 °C
  • Parameterizable via IO-Link
  • Analog output 4…20 mA (2-wire)
  • Switching output
  • Compression fitting process connection
  • Bendable probe (min. bending radius: 3x outer diameter; excluding 30-mm probe tip)

Functional principle

The TTM miniature transmitters are available with integrated probe. Due to the integrated electronics, the limited temperature range must be observed, especially in the area of the M12 connector.

Analog output

Load≤ [(V – 10 V)/21 mA] kΩ
Loadsupply
Current output4…20 mA
Repeatability0.1 % of full scale applies to temperatures > +300 °C
Repeatability0.1 K
NoteConnection to PIN 1+2
Accuracy± 0.3 K

Reference conditions acc. to IEC 61298-1

Auxiliary power24 VDC
Humidityfrom 45 to 75 %
Atmospheric pressurefrom 860 to 1060 hPa
Temperatur (-)15…+25 °C

Programming FDT / DTM

Transmission rateCOM 2 / 38.4 kbps
Transmission physicscorresponds to 3-wire physics (PHY2)
Frame type2.2
Process data width16 bit
Included in the SIDI GSDMLYes
Switchpoint information1 bit
Measured value information15 bit
Accuracy± 0.2 K

Power supply

Short-Circuit/Reverse Polarity ProtectionIP67
Voltage drop at Ieyes / yes
Electricity consumptionup to 20 mA
Operating voltagefrom 8 to 32 V
Degree of protection (IP)IP67
Electrical safety classIII

Temperature behaviour

Temperature coefficient zero point TK0± 0.1 % of full scale/10 K
Temperature coefficient range TKs± 0.1 % of full scale/10 K

Tests/approvals

MTTF541 years acc. to SN 29500 (Ed. 99) 40
MTTF°C

Mechanical data

Sensor materialStainless steel, 1.4404 (AISI 316L)
Elektrischer AnschlussConnector, M12 × 1
Pressure resistance100 bar
Process connectionFor compression fittings, thermowell or
Process connectiondirect mounting
Housing materialStainless-steel/Plastic, 1.4404 (AISI
Housing material316L)

Switching outputs

Switching point accuracy± 0.3 K
Release position-210…+640 °C
Switching point-200…+650 °C
Switching cycles≥ 100 mil.
Output functionNO/NC programmable, PNP/NPN
NoteConnection to PIN 1+3+4. Please use
Notea 3-wire cable for operation on a Turck
NoteTBEN IO-Link master.
Communication protocolIO-Link
Rated operating current0.15 A

Temperature range

Outer diameter6 mm
Response timet₀₅ = 1.5 s / t₀₉ = 6.0 s in water @ 0.2 m/s
Immersion depth L600 mm
NoteMax. temperature of electronics:
Note80 °C/176 °F
Factory setting0…150 °C
Factory setting32…302 °F
Accuracy±0.15 K + 0.002 ∙ |t| (-30…300 °C)
Measuring range-50…350 °C
Measuring range-58…662 °F
Messelement (nach DIN IEC 751)Pt100, DIN EN 60751, class A

Ambient Conditions

Ambient temperaturefrom -40 to 80 °C
Storage temperaturefrom -40 to 80 °C

Output

Output 1Switching output or IO-Link mode
Output 2Analog output

IO-Link

IO-Link specificationV 1.1

Other

Process connectionRohrverschraubung
Housing materialEdelstahl
Housing materialKunststoff
Analog output4…20 mA
Connector typeM12
Switching outputSchließer/Öffner
Switching outputPNP
Switching outputNPN