Features

  • 2 transistor outputs (ð 10kHz)
  • Switchable: 2-channel or signal doubling
  • Output mode adjustable (NO/NC mode)
  • Input circuits monitored for wire-break/ short-circuit (ON/OFF switchable)
  • Complete galvanic isolation
  • Input reverse-polarity protected
  • Removable screw terminals
  • ATEX, IECEx, NEPSI, cUL, cFM, INMETRO, Kosha, TIIS, DNV, GL
  • Use in Zone 2
  • SIL 2

Semiconductor output circuits

Switching current per output≤ 0.1 A
Voltage drop≤ 1.1 V at 20 mA, ≤ 1.8 V at 50 mA, ≤ 2.7 V at 100
Voltage dropmA
Switching frequencyup to 10000 Hz
Output circuits2 x transistor (potential-free, short-circuit proof)
Switching voltageup to 30 V

Galvanic separation

Output 1 to output 2100 V RMS acc. to EN 50178 and EN 61010-1
Output 1 to supply100 V RMS acc. to EN 50178 and EN 61010-1
Test voltage2.5 kV RMS
Input 2 to output 2375 V peak value acc. to EN 60079-11
Application areaII (1) G, II (1) D
Application areaII 3 (1) G
Output 2 to supply100 V RMS acc. to EN 50178 and EN 61010-1
Ignition protection category[Ex ia Ga] IIC; [Ex ia Da] IIIC
Ignition protection typeEx nA [ia Ga] IIC T4 Gc
Input 1 to supply375 V peak value acc. to EN 60079-11
Input 1 to output 1375 V peak value acc. to EN 60079-11
Use in SIL safety circuitsSIL 2 acc. to IEC 61508
Ex approval acc. to conformity certificateTÜV 14 ATEX 147004 X
Input 2 to supply375 V peak value according to EN 60079-11
Important noteFor Ex-applications the values specified in the corresponding Ex certificates (ATEX, IECEx, UL, etc.) apply.
Important noteIf the device is used in applications to achieve functional safety according to IEC 61508, the safety
Important notemanual must be used. Information in the data sheet
Important noteare not valid for functional safety.

NAMUR input

Wire breakage threshold≤ 0.06 mA
Switch-on threshold1.75 mA
Short-circuit current8.2 mA
Input resistance1 kΩ
Switch-off threshold1.55 mA
Short-circuit threshold≥ 6.4 mA
No-load voltage8.2 VDC
NAMUREN 60947-5-6
Line Resistance≤ 50 Ω
Input circuit monitoringon/off switchable

Displays/Operating elements

Operational readinessGreen
Switching stateYellow
Error indicationred

Allgemein

Nominal voltage24 VDC
Power dissipation, typical≤ 0.64 W
Inputs2-channel or 1-channel with signal doubling
Operating voltagefrom 10 to 30 V
Power consumptionup to 0.8 VA

Mechanical data

AltitudeUp to 2000 m above sea
Altitudelevel
Pollution degreeII
Overvoltage categoryII (EN 61010-1)