HomeSensor AnalyticsFieldbus Modules100001826
TurckCompact PROFIsafe / PROFINET Block I/O Module Safe Digital Inputs and Outputs – Image 1
Turck

Compact PROFIsafe / PROFINET Block I/O Module Safe Digital Inputs and Outputs

SKU: 100001826 Type: TBPN-L5-4FDI-4FDX
Available3–5 business days delivery
€913.00 / pieces
€1,086.47 incl. VAT

These are our list prices.Get an individual quote within 24 h.

Request a quote
Data sheet

Features

  • PROFINET device
  • Integrated Ethernet switch
  • 100 Mbps supported
  • 2 × M12, 4-pin, D-coded, Ethernet fieldbus connection
  • Glass fiber reinforced housing
  • Shock and vibration tested
  • Fully potted module electronics
  • Protection classes IP65, IP67, IP69K
  • 5-pin 7/8″ male connector for power supply
  • ATEX zone 2/22
  • CCC-Ex
  • Four secure digital SIL3 inputs
  • Four secure configurable digital SIL3 inputs or outputs Figure 1

General Information

Mounting2 mounting holes ￿ 6.3 mm
MountingThe data sheet serves as advance information. For
Mountingdefinitive values see the corresponding product
Mountingmanual. In this respect, no liability for completeness
Mountingand accuracy can be applied to the content of this
Mountingdata sheet.
ERRGreen On Diagnostics disabled
ERRRed On Diagnostics enabled
Halogen freeyes
Ambient temperaturefrom -40 to 70 °C
Connector materialNickel-plated brass
Material screw303 stainless steel
Dimensions (L x W x H)60.4 x 230.5 x 38.8 mm
Housing colourBlack
ETH1/ETH2Green On Ethernet Link (100 Mbps)
ETH1/ETH2flashing Ethernet communication (100 Mbps)
ETH1/ETH2Off No Ethernet link
Storage temperaturefrom -40 to 85 °C
PWRGreen On V power supply OK
PWR1
PWROff V power supply off or below defined threshold of 18 V
Window materialLexan
AltitudeMax. 5000 m
LEDColor Status Description
Housing materialPA6-GF30
Material labelPolycarbonate
BUSGreen On Active connection to a master
BUSflashing Ready
BUSRed On IP-address conflict or Restore Mode or Modbus timeout
BUSflashing Blink/Wink command active
BUSRed/Green Alternating Autonegotiation or waiting for DHCP/Boot-P addressing
Degree of protection (IP)IP67
Degree of protection (IP)IP69K
Degree of protection (IP)IP65

Safety outputs (OSSDs)

Actuator power supply2 A (resistive)
Actuator power supply1 A (inductive)
Output current in off state< 5 V
Output current in off state< 1 mA
Output current in off statesuitable for inputs according to EN 61131-2 Type 1
Test pulse, typical0.5 ms
Test pulse, typical1.25 ms
Input delayM12, 5-pin
Test pulse, maximum500 ms
Max. output currentThe load must be mechanically or electrically inert to
Max. output currenttolerate the test pulses.
Max. output currentWhen configured as a PPM switching output the
Max. output currentnegative pole of the load should be wired to the Mterminal of the corresponding output (Pin 2).
Additional InformationM12, 5-pin
Interval between 2 test pulses, minimum250 ms
Interval between 2 test pulses, minimumPower supply V AUX1/T1 max. 2 A
Interval between 2 test pulses, minimumPlease consider derating as shown in figure 1
Connectivity inputs2.5 ms

LED Status I/O

0…7Green On Channel active
0…7flashing Self test
0…7Red On Discrepancy
0…7flashing Cross circuit
8…15Green On Channel active
8…15flashing Self test (input only)
8…15Red On Discrepancy, overload (output only)
8…15flashing Cross circuit

System data

Web serverintegrated
Transmission rate fieldbus100 Mbps
Service interfaceEthernet via P1 or P2
Connection technology fieldbus2 × M12, 4-pin, D-coded

PROFINET

AddressingDCP
Diagnosticsacc. to PROFINET alarm handling
Topology detectionsupported
MinCycleTime1 ms
Automatic addressingsupported
Media Redundancy Protocol (MRP)supported
Conformance classB (RT)

Safety Inputs OSSD

Max. tolerance test pulse width1 ms
Low-level signal voltageEN 61131-2 Type 1 ( < 5 V; < 0.5 mA)
Max. OSSD supply per channel2 A per C0 to C7,
Max. OSSD supply per channel1.5 A at 70 °C
Max. OSSD supply per channelPlease consider derating as shown in figure 1
High level signal voltageEN 61131-2 Type 1 ( > 15 V; > 2 mA)
Interval between 2 test pulses, minimum20 ms at 1 ms test pulse width
Interval between 2 test pulses, minimum15 ms at 0.5 ms test pulse width

Supply

Admissible range20.4…28.8 VDC
Power dissipation, typical≤ 5 W
Electrical isolationgalvanic isolation of the voltage groups V1 and V2,
Electrical isolationvoltages up to 500 VAC
Supply voltage24 VDC
Connection technology power supply7/8″, 5-pin

Safety Data

PL according to EN ISO 13849-1Level e
Category according to ISO 13849-1:20084
Useful Lifetime20 years (EN ISO 13849-1)
SIL according to IEC 615083

Safety Inputs floating/antivalent

Test pulse, typical0.6 ms
Sensor supplyPower supply V AUX1/T1 max. 2 A
Sensor supplyPlease consider derating as shown in figure 1
Test pulse, maximum0.8 ms
Additional InformationNo connection to external potential allowed
Max. cable lengthup to 1 m
Max. loop resistance< 150 Ω
Interval between 2 test pulses, minimum900 ms

Standard/Directive conformity

Directive2006/42/EC Machine Directive
Directive2014/35/EC Low Voltage Directive
Directive2014/30/EC EMC Directive
Shock testacc. to EN 60068-2-27
Approvals and certificatesCEUKCAATEX zone 2/22
Approvals and certificatesCCC-Ex
Approvals and certificatesFCC statement,
Approvals and certificatesUV resistant acc. to DIN EN ISO 4892-2A (2013)
Vibration testAcc. to EN 60068-2-6
Vibration testAcceleration up to 20 g
UL CertificatecULus LISTED 21 W2, Encl.Type 1 IND.CONT.EQ.
Drop and toppleacc. to EN 60068-2-31/IEC 60068-2-32
Note on ATEX/IECExThe Quick Start Guide with information on use in Ex
Note on ATEX/IECExareas must be observed.
Electromagnetic compatibility (EMC)Acc. to EN 61131-2

Power supply

Supply voltage24 VDC

Other

Housing materialKunststoff