HomeSensor AnalyticsFieldbus Modules100002597
TurckI/O Hub for Connection of Digital Signals to IO-Link Master 8 Digital Inputs, 4 M12 Ports – Image 1
Turck

I/O Hub for Connection of Digital Signals to IO-Link Master 8 Digital Inputs, 4 M12 Ports

SKU: 100002597 Type: TBIL-S4-8DIP
Available3–5 business days delivery
€123.80 / pieces
€147.32 incl. VAT

These are our list prices.Get an individual quote within 24 h.

Request a quote
Data sheet

Features

  • Glass fiber reinforced housing
  • Shock and vibration tested
  • Fully potted module electronics
  • Protection classes IP65, IP67, IP69K

General Information

Mounting2 mounting holes, Ø 4.3 mm
MTTF560 years acc. to SN 29500 (Ed. 99) 20 °C
IO-LinkGreen OFF Power off
IO-LinkFlashing IO-Link communication OK,
IO-Linkvalid process data is being sent or received
IO-LinkRed ON IO-Link communication or module error
IO-Linkinvalid process data or diagnosis enabled
Ambient temperaturefrom -40 to 70 °C
Dimensions (L x W x H)32 x 144.3 x 32 mm
Housing colourBlack
LED displayColor Status Description
Storage temperaturefrom -40 to 85 °C
AltitudeMax. 5000 m
Housing materialPA6-GF30
Degree of protection (IP)IP67
Degree of protection (IP)IP69K
Degree of protection (IP)IP65

IO-Link

Transmission rateCOM 2/38.4 kbps
IO-Link port typeClass A
Frame type2,6
Connectivity IO-Link1 × M12
IO-Link specificationV 1.1

Supply

Admissible range18…30 VDC
Sensor/actuator supplyClass A supply from V1
Sensor/actuator supplyShort-circuit proof, 4 A per port
Operating current120 mA
Supply voltage24 VDC
Connection technology power supplyM12

Digital inputs

Number of channels8
Sensor supply0.5A
Input delay0.010 ms
Low-level signal voltage-3…5 VDC (EN 61131-2, type 1 and 3)
Max. input current15 mA
Type of input diagnosticsChannel diagnostics
High level signal voltage11…30 VDC (EN 61131-2, type 1 and 3)
Connectivity inputsM12

I/O LED Status

Cx – CxGreen ON Input or output active
Cx – CxRed ON Output active with overload/short circuit
Cx – CxFlashing Power overload at the corresponding port. Both port LEDs are flashing.
Cx – CxOFF Input or output inactive

Standard/Directive conformity

Shock testacc. to IEC 60068-2-27
Approvals and certificatesCEUKCAUV resistant acc. to DIN EN ISO 4892-2A (2013)
Vibration testAcc. to IEC 60068-2-6
UL CertificatecULus LISTED 21 W2, Encl.type 1 IND.CONT.EQ.

Power supply

Supply voltage24 VDC

Other

Housing materialKunststoff