Processor Unit – For the Connection of FP Product Series Non-Ex Flow Sensors IO-Link Device with Current and Transistor Switching Outputs
Features
- • Analog output for flow
- • Transistor switching outputs for temperature and faults
- • Teaching upper and lower flow limit
- • LED band for indication of flow rate and media temperature
- • Monitoring of operating and display range
- • Detection of wire-break and short-circuit on the sensor side
- • Standard IO or IO-Link operating mode
- • Parametrized via pushbutton or software-supported via IO-Link
Functional principle
With the external processing unit type FM-IM- …FX, all non-Ex flow sensors of the FP100 series (immersion sensors) can be operated. The flow module features four status LEDs as well as a 10-segment LED band for local monitoring. Software-based diagnostic options are also available to the user, such as wirebreak and short-circuit on the sensor side. Furthermore, monitoring of flow rates and media temperatures within a predefined operating and display range. The upper and lower limit are determined in relation to the analog output signal and taught in using the implemented teach mode. Working on the calorimetric principle, the connectible sensors not only detect the flow rate but also the media temperature. The flow module can be operated either in IO-Link (IOL) or in standard IO (SIO) mode via the integrated IO-Link interface. In SIO mode, the switching outputs are operated in the standard way. In IOL mode the current process signal is transmitted cyclically as a 10 bit-serial value. Parametrization is initiated either via pushbutton or software-supported via IOLink interface. The actual parametrization is then implemented via the tool-based DTM or IODD within the FDT frame PACTware™ or acyclically near the control via On-Request Data Objects (ORDO).
Customizable output functions
| Error recognition | NAMUR error limits |
| Current range | 4…20 mA / 20…4 mA parametrizable |
| Display switch state | active high / active low parametrizable |
| Display switch state | (transistor output error monitoring only |
| Display switch state | active low) |
| Switching characteristic | PNP |
| Load | < 600 Ω |
| Error monitoring | transistor output |
| Characteristic | Output of probe signal, no linearization |
| Flow Monitoring | Analog output |
| Electrical connections | 5-pole removable reverse polarity protected terminal blocks |
| Type of fastening | screw connection |
| Temperature monitoring | transistor output |
| Switching current | 100 mA |
| Terminal cross-section | ≥ 1.5…≤ 2.5 mm² |
| Switching voltage | from 20 to 30 V |
Mechanical data
| Flow | yellow on Active current output |
| Flow | flashing Teach mode / display of diagnostic data |
| Flow | for specification see manual |
| Flow | Value 10 Bit (Bit 15 = MSB, Bit 6 = LSB) not assigned Out 3 Out 2 Out1 |
| Flow | (Fault) (Temp) (Flow) |
| Temp | yellow off Switching output media temperature [low] |
| Temp | on Switching output media temperature [high] |
| Temp | flashing Teach mode / display of diagnostic data |
| Temp | for specification see manual |
| MTBF | 117 Years |
| Mounting method | DIN rail mounting and mounting panel |
| Bit 15 | 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 |
| Ambient temperature | from -25 to 70 °C |
| Design | Signal processor |
| PWR | green on Operating voltage applied |
| PWR | Device ready for operation |
| PWR | flashing Operating voltage applied |
| PWR | IO-Link communication active |
| PWR | (inverted flash with T on 900 ms and T off 100 ms) |
| LED displa | y |
| LED | Color Status Description |
| Housing material | Plastic, Polycarbonate/ABS |
| Fault | Red Off Switching output fault [high] |
| Fault | On Switching output flow [low] |
| Fault | (for error pattern in combination with LEDs see manual) |
| For detaile IM/FMX-IM IO-Link (Pr | d description of the display patterns and flashing codes see instructi |
| For detaile IM/FMX-IM IO-Link (Pr | ocess Data Objects) |
| Degree of protection (IP) | IP20 |
| Abmessung | 89 x 110 x 27 mm |
IO-Link
| Transmission rate | 38.4 kBit/s (COM 2) |
| Communication modes | Tool based engineering via FDT / DTM, |
| Communication modes | IODD. Acyclic communication via On-Request Data Objects |
| Included in the SIDI GSDML | Yes |
| Communication channel | Clamp 12 and via front panel jack COM |
| Communication channel | (PC) |
| IO-Link specification | V 1.1 |
Electrical data
| Measurement frequency | 5 Hz (every 200 ms with software filter) |
| Sensor current limitation | approx. 110 mA |
| Repeatability media temperature | typical ± 1 K |
| Medium temperature | [°C] with the SET button temporarily |
| Medium temperature | pressed |
| Measuring accuracy media temperature | typical ± 7 K |
| Sensor current | ≤ 35 mA |
| Sensor voltage | ≤ 15 VDC |
| No-load current I0 | ≤ 63 mA |
| Teach modes | Min/max adjustment. Teach modes incl. |
| Teach modes | DeltaFlow monitoring (teach modes are |
| Teach modes | automatically released with the change of |
| Teach modes | flow speed). |
| Input function | Connection of flow sensors (non-Ex sensors of the FP100/FP150 product series |
| Input function | only!) |
| Flow speed | [%] after min/max adjustment (permanent) |
| Switchpoint hysteresis media temperature | 2 K |
| Repeatability flow rate | typical ± 1 % (of full scale) |
| Operating voltage UB | from 20 to 30 VDC |
| Power consumption | up to 4.5 VA |
Tests/approvals
| Relative humidity | EN 60068-2-38 |
| Approvals | CE |
| Approvals | C-UL U.S. submitted |
| Electromagnetic compatibility (EMC) | Acc. to NE21 |
ausgangsfunktionen
| Switching current | 100 mA |
| Switching voltage | from 20 to 30 V |