HomeSensor AnalyticsSensor Evaluation7525104
Turck Processor Unit – For the Connection of FCS and FCI Product Series Flow Sensors IO-Link Device with Current and Transistor Switching Outputs – Image 1
Turck

Processor Unit – For the Connection of FCS and FCI Product Series Flow Sensors IO-Link Device with Current and Transistor Switching Outputs

SKU: 7525104 Type: FM-IM-2UPLI63X
Available 3–5 business days delivery
€302.20 / pieces
€359.62 incl. VAT
Data sheet

Features

  • Analog output for flow
  • Transistor switching outputs for temperature and faults
  • Teaching upper and lower flow limit
  • LED band for indication of flow rate and media temperature
  • Monitoring of operating and display range
  • Detection of wire-break and short-circuit on the sensor side
  • Standard IO or IO-Link operating mode
  • Parametrized via pushbutton or software-supported via IO-Link

Customizable output functions

Error recognition NAMUR error limits
Current range 4…20 mA / 20…4 mA parametrizable
Display switch state active high / active low parametrizable
Display switch state (transistor output error monitoring only
Display switch state active low)
Switching characteristic PNP
Load < 600 Ω
Error monitoring transistor output
Characteristic Output of probe signal, no linearization
Flow Monitoring Analog output
Electrical connections 5-pole removable reverse polarity protected terminal blocks
Type of fastening screw connection
Temperature monitoring transistor output
Switching current 100 mA
Terminal cross-section ≥ 1.5…≤ 2.5 mm²
Switching voltage from 20 to 30 V

Mechanical data

Flow yellow on Active current output
Flow flashing Teach mode / display of diagnostic data
Flow for specification see manual
Flow Value 10 Bit (Bit 15 = MSB, Bit 6 = LSB) not assigned Out 3 Out 2 Out1
Flow (Fault) (Temp) (Flow)
Temp yellow off Switching output media temperature [low]
Temp on Switching output media temperature [high]
Temp flashing Teach mode / display of diagnostic data
Temp for specification see manual
MTBF 117 Years
Mounting method DIN rail mounting and mounting panel
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Ambient temperature from -25 to 70 °C
Design Signal processor
PWR green on Operating voltage applied
PWR Device ready for operation
PWR flashing Operating voltage applied
PWR IO-Link communication active
PWR (inverted flash with T on 900 ms and T off 100 ms)
LED displa y
LED Color Status Description
Housing material Plastic, Polycarbonate/ABS
Fault Red Off Switching output fault [high]
Fault On Switching output flow [low]
Fault (for error pattern in combination with LEDs see manual)
For detaile IM/FMX-IM IO-Link (Pr d description of the display patterns and flashing codes see instructi
For detaile IM/FMX-IM IO-Link (Pr ocess Data Objects)
Degree of protection (IP) IP20
Abmessung 89 x 110 x 27 mm

IO-Link

Transmission rate 38.4 kBit/s (COM 2)
Communication modes Tool based engineering via FDT / DTM,
Communication modes IODD. Acyclic communication via On-Request Data Objects
Included in the SIDI GSDML Yes
Communication channel Clamp 12 and via front panel jack COM
Communication channel (PC)
IO-Link specification V 1.0

Electrical data

Measurement frequency 5 Hz (every 200 ms with software filter)
Sensor current limitation approx. 110 mA
Repeatability media temperature typical ± 1 K
Medium temperature [°C] with the SET button temporarily
Medium temperature pressed
Measuring accuracy media temperature typical ± 7 K
Sensor current ≤ 35 mA
Sensor voltage ≤ 15 VDC
No-load current I0 ≤ 63 mA
Teach modes Min/max adjustment. Teach modes incl.
Teach modes DeltaFlow monitoring (teach modes are
Teach modes automatically released with the change of
Teach modes flow speed).
Input function Connection of flow sensors (non-Ex sensors of the FCS/FCI product series only!)
Flow speed [%] after min/max adjustment (permanent)
Switchpoint hysteresis media temperature 2 K
Repeatability flow rate typical ± 1 % (of full scale)
Operating voltage UB from 20 to 30 VDC
Power consumption up to 4.5 VA

Tests/approvals

Relative humidity EN 60068-2-38
Approvals CE
Approvals C-UL U.S. submitted
Electromagnetic compatibility (EMC) Acc. to NE21

ausgangsfunktionen

Switching current 100 mA
Switching voltage from 20 to 30 V