| Seal | FPM |
| Sensor material | Stainless steel, 1.4571 (AISI 316Ti) |
| Elektrischer Anschluss | Connector, M12 × 1 |
| Correct installation | To retrieve the full performance potential of the sensor, it must be aligned correctly. In |
| Correct installation | particular when monitoring bad heat-conductive media such as oils, liquids with high |
| Correct installation | solids, abrasive media, etc., when exposed to fast temperature changes (K/min) and, |
| Correct installation | in general, near components with analog output. |
| Correct installation | Correct installation is ensured, as soon as the effective flow direction of the application matches the direction of flow indicated by the "arrow" on the sensor. |
| Pressure resistance | 100 bar |
| Mounting Adapter | The freely rotatable flow sensors are mounted with the FCA-FCST adapter. The |
| Mounting Adapter | adapter is screwed in a T piece or a welding sleeve and sealed accordingly. When |
| Mounting Adapter | assembling adapters with cylindrical thread, use the enclosed seal (e.g. G1/4, G1/2, |
| Mounting Adapter | G3/4, etc.). Mounting adapters with NPT-thread are generally delivered without seal |
| Mounting Adapter | (e.g. N1/2). Use hemp or teflon tape |
| Mounting Adapter | The sensor is fixed in the adapter by means of a captive nut fitted between the upper |
| Mounting Adapter | housing part and the cone seat. |
| Process connection | M18 × 1.5 female thread |
| Design | Immersion |
| Housing material | Stainless steel, 1.4571 (AISI 316Ti) |
| Mounting position | In order to minimize potential misinterpretations due to disturbance, it is recommended to position the sensor with a minimum separation distance of 3 x di before and 5 x |
| Mounting position | di after bends, changes in cross section, valves, etc.. |
| Mounting position | ■If the flow channel is not completely filled with the medium, it is recommended to install the sensor from underneath. |
| Mounting position | ■If deposits are likely to built up, it is recommended to install the sensor on the side. |
| Mounting position | It is important to note that deposits can also form on the tip, which may affect the |
| Mounting position | monitoring results. Therefore, it is recommended to clean the sensor at regular intervals and to select the associated service interval accordingly. |
| Mounting position | ■If blistering is to be expected, ensure that there is no air bubble located in the area |
| Mounting position | of the tip when installing the sensor. |
| Mounting position | ■If the sensor is mounted in vertical piping systems, it is recommended to position |
| Mounting position | the sensor within the riser. |